The optimal basis for the digital challenges of the process industry.
In any facility, space comes at a premium. And at a cost. Our response is the SIMATIC ET 200SP HA. The compact, modular periphery creates space in the control panel, providing advantages for system designers and operators. Its highly scalable structure makes it possible to precisely align expansions in the control panel with actual needs. And tool-free connection using push-in terminals and fixed wiring cuts the costs of engineering, assembly and wiring.
In any facility, space comes at a premium. And at a cost. Our response is the SIMATIC ET 200SP HA. The compact, modular periphery creates space in the control panel, providing advantages for system designers and operators. Its highly scalable structure makes it possible to precisely align expansions in the control panel with actual needs. And tool-free connection using push-in terminals and fixed wiring cuts the costs of engineering, assembly and wiring.
1. Components
The system basically consists of the following components:
- Carrier modules for interface modules: The carrier modules are used for the electrical and mechanical connection of the individual modules.
- Interface modules (IM) for connection to PROFINET single or redundant. The fieldbus is connected via the Busadapter (BA), which allows connection technology and physics to be freely selected according to the application requirements.
- Server module closes the station.
- Carrier modules for I/O modules: By connecting the carrier modules to the terminal blocks, the slots for the I/O modules are created.
- Terminal blocks: The terminal blocks provide the process terminals for connecting the sensors, actuators and other devices.
- I/O modules determine the function of the module at the terminals. I/O modules are subdivided into module types. These are characterized in each case by modul-type-specfic and colored square printed on the front.
- Digital input (DI), color: white
- Digital output (DQ), color: black
- Analog input (AI), color: light blue
- Analog output (AQ), color: dark blue
- Analog/Digital (CIQ), color: grey
- Accessories (opional)
- Labeling strips and color identification labels are offered for individual labeling.
- For the color identification of the potentials defined by the plugged I/O module, there are module-specific color identification labels.
- A shield connection is available for fast, low-impedance connection of cable shields.
2. Order numbers
Product | Order number |
---|---|
I/O modules | |
ET 200SP HA, AI 16xI 2-WIRE HART | 6DL1134-6TH00-0PH1 |
ET 200SP HA, AI16xTC/8xRTD 2-/3-/4-WIRE | 6DL1134-6JH00-0PH1 |
ET 200SP HA, AI-DI16/DQ16x24VDC HART | 6DL1133-6EW00-0PH1 |
ET 200SP HA, AQ 8xI HART HA | 6DL1135-6TF00-0PH1 |
ET 200SP HA, DI 16x24VDC | 6DL1131-6BH00-0PH1 |
ET 200SP HA, DI 8x230VAC | 6DL1131-6GF00-0PK0 |
ET 200SP HA, DI 8×24 …125VDC HA | 6DL1131-6DF00-0PK0 |
ET 200SP HA, DI16x NAMUR | 6DL1131-6TH00-0PH1 |
ET 200SP HA, DQ 16x24VDC/0,5A | 6DL1132-6BH00-0PH1 |
ET 200SP HA, RQ 4x24VUC 230VAC/5A Changer | 6DL1132-6HD50-0PK0 |
Carrier modules | |
Carrier module IM redundant with server module | 6DL1193-6BH00-0RM0 |
Carrier module IM single with server module & IM cover | 6DL1193-6BH00-0SM0 |
Carrier module for 2 I/O modules from a ET 200SP HA | 6DL1193-6GA00-0NN0 |
Carrier module for 8 I/O modules from a ET 200SP HA | 6DL1193-6GC00-0NN0 |
Interface modules | |
IM 155-6 PN | 6DL1155-6AU00-0PM0 |
Busadapter | |
ET 200SP HA, Busadapter 2xRJ45 | 6DL1193-6AR00-0AA0 |
ET 200SP HA, Busadapter 2xFC | 6DL1193-6AF00-0AA0 |
ET 200SP HA, Busadapter 2xLC | 6DL1193-6AG00-0AA0 |
Server modules | |
ET 200SP HA, server module (spare part) | 6DL1193-6PA00-0AA0 |
Mounting rails | |
Mounting rail 482mm (19″) | 6DL1193-6MC00-0AA0 |
Mounting rail 1500mm (59″) | 6DL1193-6MD00-0AA0 |
Terminal blocks | |
Terminal block TB22-P16+A0+4B (dark colored) | 6DL1193-6TP00-0BK0 |
Terminal block TB22-P16+A0+4D (light colored) | 6DL1193-6TP00-0DK0 |
Terminal block TB22-P32+A0+4B/T (dark colored) | 6DL1193-6TP00-0BH1 |
Terminal block TB22-P32+A0+4D/T (light colored) | 6DL1193-6TP00-0DH1 |
Terminal block TB45R-P32+A0+4B/T (dark colored) | 6DL1193-6TP00-0BM1 |
Terminal block TB45R-P32+A0+4D/T (light colored) | 6DL1193-6TP00-0DM1 |
Cover | |
5 TM-Cover, 22,5MM, to protect empty PM slots | 6DL1133-6CV22-0AM0 |
5 IM-Cover, 50MM, to protect empty IM slots | 6DL1133-6CV50-0AM0 |
Labeling stripes | |
450 Labeling stripes, light grey, 10 sheets DIN A4, perforated, paper 280g/m² | 6DL1193-6LA00-0AA0 |
500 Labeling stripes, light grey, roll with 500 labels | 6DL1193-6LR00-0AA0 |
Color identification labels | |
10 color identifications labels, color code CC00 | 6DL1193-6CP00-2HH1 |
10 color identifications labels, color code CC01 | 6DL1193-6CP01-2HH1 |
10 color identifications labels, color code CC02 | 6DL1193-6CP02-2HH1 |
10 color identifications labels, color code CC40 | 6DL1193-6CP40-2HK0 |
10 color identifications labels, color code CC42 | 6DL1193-6CP42-2HK0 |
3. Benefits
Ease of use
Ease of use The SIMATIC ET 200SP HA impresses with its especially simple installation and assembly. The new terminal block layout and the push-in technology make tool-free wiring possible. Higher flexibility during the installation in the control cabinet is possible due to the separation of mechanical and elec tronical components, allowing the station to be prewired without I/O modules. Slot covers can be inserted on the integrated terminal blocks, which can be replaced at any time. In addition, the online station expansion of the SIMATIC ET 200SP HA offer advantages in terms of system flexibility and plant availability. Benefit from the seamless integration in SIMATIC PCS 7. The SIMATIC ET 200SP HA with the Advanced Process Library offers flexible and simple online parameterization and selection of up to four HART variables on each channel of an I/O module.
Maximum availability
Plant downtime considerably reduces the economic efficiency of process plants. Redundant, flexible components significantly increase the availability of the plant. Besides operating the SIMATIC ET 200SP HA station redundantly via the PROFINET interface, there is also the possibility of a redundant set up of the I/O modules. This is realized by using a terminal block for integrated I/O redundancy which results in both economy of space and cost efficiency. With the new design and its standardized terminal blocks, redundant and single wiring are related to the same wiring effort.
Compact design
The compact size with up to 56 peripheral modules per station and the high channel density of up to 32 channels on a 22.5 mm wide module reduces the space requirement in the control cabinet to a minimum.
Ready for the field
- For installation in hazardous areas up to zone 2
- Extended temperature range: -40 to +70°C
- Enhanced interference immunity according to NAMUR recommendation NE21
- Conformal coating of all components
- Can be used up to an altitude of 4 000 meters
4. Engineering
Capacity limits
The following limit values apply to the IM155-6PN interface module:
- I/(O modules: max. 56
- Adress space: max. 1440 Byte
Note
The SIMATIC ET 200SP HA will be on sale from June 2017. System requirements are SIMATIC PCS 7 V9.0, S7-410 and PROFINET.